Commercial Electrical, Hvac/Mechanical work permitted December 2, 2024, with 2 permits through March 27, 2025. Contractor on record: MJR TECHNOLOGIES, INC dBA: GT TELECOM.
• Demo existing chiller circuits (power and control) back to 1st junction box in line (believe power conduit is shared by other circuits). • Tap the bus of 1200amp distribution panel/switchgear (surveyed panel) and install (1) 400amp fusible disconnect fused at 400amp (MOCP of the new chiller) next to distribution panel. • Install 2 ½” EMT and 250MCM circuit (sized to Chiller MCA) from 400amp disconnect to new mag bearing chiller location and finish off run to chiller integral disconnect furnished by manufacturer in greenfield flexible conduit. • Re-use conduit and 40amp wire feeding…
Philadelphia permit records name MJR TECHNOLOGIES, INC dBA: GT TELECOM and Fluidics Inc as the contractors on this project.
Phone numbers and the property owner are included with Pro, where the city publishes them.
2 permits issued Dec 2 – Mar 27, newest first.
| Issued | Permit | Contractor | Value |
|---|
Commercial and multifamily, biggest first.
#EP-2024-011907 Electrical Permit · Addition and/or Alteration • Demo existing chiller circuits (power and control) back to 1st junction box in line (believe power conduit is shared by other circuits). • Tap the bus of 1200amp distribution panel/switchgear (surveyed panel) and install (1) 400amp fusible disconnect fused at 400amp (MOCP of the new chiller)… Status: Completed | MJR TECHNOLOGIES, INC dBA: GT TELECOM | — | |
#MP-2024-005282 Mechanical / Fuel Gas Permit · Addition and/or Alterations For replacing the chiller as per approved plans. Separate permit required for electrical work. Status: Completed | Fluidics Inc | — |